| i1P | Function | |-------|-----------| | oP | Door switch – normal open | | cL | Door switch – normal closed | | EAL | External alarm (generic) | | bAL | Serious alarm (compressor stop) | | PAL | Pressure switch alarm | | dor | Door switch with fan cut-off and defrost inhibition |

If configured as dor (door switch): opening the door stops fans and displays dA after a delay (parameter doA ). Closing the door restarts normal operation. The XW60LS flashes an alarm code on the display while the red LED blinks. dixell xw60ls manual

Introduction The Dixell XW60LS is a sophisticated microprocessor-based electronic controller designed primarily for medium and low temperature refrigerating units . Manufactured by Emerson’s Dixell division (now part of Copeland), this controller is widely used in commercial refrigeration, cold rooms, industrial freezers, and HVAC applications. It is known for its robust input/output configuration, hot key programming capability, and advanced defrost management. | i1P | Function | |-------|-----------| | oP

| Parameter | Value | |-----------|-------| | Set | 2°C | | Hy | 4°C (cut-in at 4°C, cut-out at 2°C) | | LS | -5°C | | US | 8°C | | tyP | 0 (electric) | | dtE | 8°C | | idF | 6 hours | | MdF | 20 minutes | | Fnc | 2 (fan with compressor, off during defrost) | | AC | 5 min | | Parameter | Value | |-----------|-------| | Set